Technical Specifications

ParameterSpecification
ModelsFP100 (up to 99 devices/loop), FP200 (up to 242 devices/loop)
Loop TypeTwo-wire signalling line circuit (SLC)
Loop WiringClass A or Class B
Operating Voltage230V AC, 50/60 Hz
Battery Backup24hr standby + 30 min alarm
DisplayLCD with LED alarm indicators
Sounder Circuits4 x supervised sounder circuits
Operating Temperature-10 to +55 C
CertificationCE (EN 54-2, EN 54-4)

Product Overview

The FP100 and FP200 form the mid-range of the ASENWARE addressable product family, designed for medium-sized commercial, educational, and industrial buildings. Compatible with the full range of ASENWARE FP-series addressable devices: optical smoke detectors, fixed-temperature and rate-of-rise heat detectors, multi-sensor detectors, manual call points, addressable input/output modules, relay modules, and isolator modules. The two-wire loop topology carries both power and data to all devices on a single pair of conductors. Class A wiring supported for maximum fault tolerance in high-consequence applications.