FP100/FP200 Addressable Fire Alarm System - English
Two-wire addressable fire alarm system, up to 242 devices per loop
⬇ Download PDFTechnical Specifications
| Parameter | Specification |
|---|---|
| Models | FP100 (up to 99 devices/loop), FP200 (up to 242 devices/loop) |
| Loop Type | Two-wire signalling line circuit (SLC) |
| Loop Wiring | Class A or Class B |
| Operating Voltage | 230V AC, 50/60 Hz |
| Battery Backup | 24hr standby + 30 min alarm |
| Display | LCD with LED alarm indicators |
| Sounder Circuits | 4 x supervised sounder circuits |
| Operating Temperature | -10 to +55 C |
| Certification | CE (EN 54-2, EN 54-4) |
Product Overview
The FP100 and FP200 form the mid-range of the ASENWARE addressable product family, designed for medium-sized commercial, educational, and industrial buildings. Compatible with the full range of ASENWARE FP-series addressable devices: optical smoke detectors, fixed-temperature and rate-of-rise heat detectors, multi-sensor detectors, manual call points, addressable input/output modules, relay modules, and isolator modules. The two-wire loop topology carries both power and data to all devices on a single pair of conductors. Class A wiring supported for maximum fault tolerance in high-consequence applications.